SIEMENS 西门子S5-135U/155U电源设置及调试安装方法

发布日期:2013-11-07 00:00

SIEMENS 西门子S5-135U/155U电源设置及调试安装方法

SIEMENS 西门子S5-135U/155U电源设置及调试安装方法:

电源装置的输入和输出:

基于西门子订货号为6ES5 955-3LF41的电源为例,下面有电源的前端面板图,详细参考图文设置电源装置

 

Inputs and 

Based on the example of the 6ES5 955-3LF41 power supply unit, the 

Outputs 

following figure shows the arrangement of inputs and outputs on the front 

 

plate of the power supply units: 

 

注意:使用电源前,对照下图,首先做一下设置:(如未设置下列3点,电源将无法正常给CPU带来启动工作的电压。)

1:用导线将4与5接通。

2: 用导线将6与17接通。

3: 用导线将7与18接通。


 

 

The following table provides an overview of the labelling and purpose of the inputs and outputs: (下表提供了对标签和输入和输出的目的,概述:)

ID 

Label 

Element 

Purpose 

AC 120V 4.5A 

AC 230V 2.6A 

Screw terminals 1, 2, 3 

(螺丝端子1,2,3)

AC connection and protective conductor 

(交流连接和保护导体)

EN 

Screw terminal 4 

Enable Power Supply Control input for power supply 

(使电源控制电源输入)

U H 

Screw terminal 5 

Supply for EN 

Input DC 24V Ext. 

(输入直流24V的分机)

Screw terminals 6 and 7 

Voltage Monitor Monitors 24 V load voltage for > 16 V 

(电压监控24 V的负载电压>16V)

Fan Warning max. 250V/3A 

Screw terminals 8, 9, 10 (relay) 

Indicates failure of a fan (故障风扇指示)

Fan Alarm max. 250V/3A 

Screw terminals 11, 12, 13 (relay) 

Indicates failure of at least two fans and inadequate air flow;

 if jumper set accordingly, output enable is the second signal source 

(指示故障至少有两个风扇和空气流动不足,

如果相应的跳线设置,输出使能是第二个信号源。)

Battery Warning max. 

250V/3A 

Screw terminals 14, 15, 16 (relay) 

Indicates that lithium battery or rechargeable battery has dropped below limit 

(该电池或可充电锂电池,低于限额下降指示)

3V = 40A 

2 test sockets 

Current measurement sockets for test purposes only; 

no continuous operation; linearity range 0.5 V/6.6 A to 3 V/40 A 

(用于测试目的电流测量插座只,

没有连续运行;线性范围0.5 V/6.6 A到3 V/40A)

Output DC 24V 2.8A 

Screw terminals 17, 18 

Enable voltage for I/O modules (启用电压I / O模块)

Ext.Batt. DC 4.5V 

2 input sockets 

Input for an external 4.5 V backup voltage

 (输入外部备份电压4.5 V)

 

LEDs and Controls Apart from the jumpers, the LEDs and controls of the power supply unit are fitted on the front plate. The following figure shows their locations: 

(LED和控制除了跳线,这些LED及电源供应器控制安装在前面板上。下图显示了它们的位置:)

The labelling and purpose of the LEDs and controls are given in the following table: (的标签及LED和控制的目的,载于下表:)

ID 

Label 

Element 

Purpose 

Voltage selector 1 

(120伏或230选择开关)

Switch 

(开关)

Voltage selector switch: choice of 120 V or 230 V 

(电压选择开关:120伏或230选择V)

Power 

Switch 

(开关)

Standby On/Off switch (not system On/Off switch) 

待机On / Off开关(不是系统开/关 开关) 

Voltage low 

(电压低报警指示灯)

Red LED 

(红色LED)

Low voltage at load voltage monitor input 

(红色LED发亮,监控到负载电压输入过低)

Fan 1 

Red LED 

(红色LED)

Failure of Fan 1  (风扇1故障)

Fan 2 

Red LED 

(红色LED)

Failure of Fan 2 (风扇 2 故障)

Fan 3 

Red LED 

(红色LED)

Failure of Fan 3 (风扇 3 故障)

Alarm 

(报警)

Red LED 

(红色LED)

Indicates failure of at least two fans of insufficient air flow 

(指示故障至少有两个不足气流风扇)

MB low 

(机架内部电池报警灯)

Yellow LED 

(黄色LED)

Lithium battery/external battery voltage below preset limit (3V) 

(锂电池/低于预设限制(3V的外部电池电压))

RB low 

(电源内部电池报警灯)

Yellow LED 

(黄色LED)

Rechargeable battery voltage below preset limit (3V) 

(下面预设限制(3V的充电电池电压)

Reset Batt.+Fan 

Pushbutton 

(复位的按键)

Reset of LEDs D, E, F, G, H, I when fault cleared 

(复位的LED  D,E,F,G这些项,电源如正常情况下,故障清除)

5V o.k. 

Green LED 

(绿色LED)

Lights up to indicate output voltage within permissible range

(绿色LED发亮的允许范围内表明输出电压正常) 

15V o.k. 

Green LED 

(绿色LED)

Lights up to indicate output voltage within permissible range 

(绿色LED发亮的允许范围内表明输出电压正常)

24V o.k. 

Green LED 

(绿色LED)

Lights up to indicate output voltage within permissible range 

(绿色LED发亮的允许范围内表明输出电压正常)

 

1) Only on the 6ES5 955-3LC42 and 6ES5 955-3LF42 

Function Selection 

Jumper 

Setting 

Application/Note 

(X) 

Battery monitor Oswitched on for 

rechargeable battery and battery 

Oswitched on for battery and off for

 rechargeable battery Oswitched off 

MM - NN 

MA - NA 

MM - NN 

MA - NA 

MM - NN 

MA - NA 

open 

open 

irrelevant 

closed 

closed 

closed 

Redundant backup 

If, for example, no redundancy is 

required in backup, i.e. 

the rechargeable battery is missing

 For example, monitoring is not needed 

for EU without backup 

 

Reaction of battery monitoring 

following battery failure O/BAU 

signal active following return of line 

voltage O/BAU signal active 

following return of line voltage and 

during operation 

MB - NB

MB - NB 

closed open 

The possibility of evaluating the battery 

monitoring during operation is 

dependent on the CPU in use 

 

After failure of more than one fan or 

inadequate air flow 

 

OPSU shutdown 

 

ONo PSU shutdown 

F-R 

 

F-R 

closed

 

open

Caution: To prevent overheating of modules, 

the PSU must be shut down after 60 s at 

the latest (for example, by time relay)

(注意:为防止模块过热,电源必须关闭

后60章在最新的(例如,通过时间继电器)

 

Voltage monitor 

 

Oswitched off 

 

Oswitched on 

BA-EX 

BA-EX 

Closed

open 

Monitoring of load voltage input switched off 

(负载电压输入监测关掉)

Monitoring of load voltage input switched on 

(负载电压输入监测开机)

 

Relay alarm 

Odriven by fan monitor and output inhibit 

(由风扇监测和输出Odriven抑制)

Odriven only by fan monitor 

(只有风扇Odriven监测 )

BB-AA 

BB-AA 

closed 

open 

Fault message initiated by fan 

fil/ihibiibfailure/output inhibit active; can 

be signaled to control room, for example.

(故障信息发起的风扇富达/ ihibiibfailure /

输出抑制活性,可以示意控制室,例如)

 Fault message initiated by fan failure; can be 

signaled to control room, for example. 

(故障信息发起的风扇故障,可以示意控

制室,例如。 )

 

The jumper locations are given in the following figure: (跳线位置给出如下图:)